Module 18 — IoT and OT Hacking · Practice Questions

Original, concept-based questions written to teach the testable ideas — not exam dumps (those violate the EC-Council Candidate Agreement and get certs revoked). Answers are collapsed: think first, then expand. Aim for ≥80% before moving on. Log misses in PROGRESS.md.

Pairs with facts.md · flashcards.csv · README.md.


Q1. An IoT sensor publishes readings to a broker, and a dashboard subscribes to receive them. The messaging is lightweight and rides over TCP. Which protocol and model is this?

  • A. CoAP, request/response over UDP
  • B. MQTT, publish/subscribe over TCP
  • C. DNP3, master/outstation over TCP
  • D. BACnet, client/server over UDP
Answer **B. MQTT, publish/subscribe over TCP.** MQTT uses a **broker** with a **pub/sub** model on **1883** (TLS **8883**). CoAP is the RESTful-over-UDP option (5683). The *broker + publish/subscribe + TCP* triad is the MQTT fingerprint. **Trap:** swap a single word (TCP↔UDP, pub/sub↔request/response) and the answer flips to CoAP.

Q2. Which statement correctly contrasts CoAP with MQTT?

  • A. CoAP is RESTful over UDP (port 5683); MQTT is publish/subscribe over TCP (port 1883)
  • B. CoAP is publish/subscribe over TCP; MQTT is RESTful over UDP
  • C. Both run over TCP on port 1883
  • D. CoAP requires a broker; MQTT is brokerless
Answer **A.** **CoAP = RESTful request/response over UDP, port 5683** (DTLS 5684). **MQTT = publish/subscribe over TCP, port 1883** (TLS 8883, broker-based). This TCP/UDP + pub-sub/REST swap is the single most-tested distinction in the module.

Q3. A utility SCADA system uses a protocol on TCP port 20000 to talk to substation devices. Which protocol is it?

  • A. Modbus
  • B. S7comm
  • C. DNP3
  • D. EtherNet/IP
Answer **C. DNP3** (port **20000**) is common in **electric and water utilities**. Modbus = **502**, S7comm = **102** (Siemens), EtherNet/IP = **44818** (Rockwell/Allen-Bradley). Like most legacy OT protocols, DNP3 ships with **no built-in authentication or encryption**.

Q4. Match the protocol to its default port. Which pairing is wrong?

  • A. Modbus → 502
  • B. S7comm → 102
  • C. BACnet → 47808
  • D. OPC UA → 44818
Answer **D is wrong.** **OPC UA = 4840**; **44818** is **EtherNet/IP** (Rockwell/Allen-Bradley). The others are correct: Modbus 502, S7comm 102 (Siemens), BACnet 47808/UDP (building automation). OPC UA is also the outlier that is **security-capable** (can authenticate and encrypt) — unlike the legacy protocols.

Q5. In the Purdue model, at which level do the PLCs, RTUs, and IEDs that run the control logic live?

  • A. Level 0
  • B. Level 1
  • C. Level 2
  • D. Level 3
Answer **B. Level 1 (Basic control).** L0 = physical process (sensors/actuators/motors/valves), **L1 = PLC/RTU/IED**, L2 = HMI/SCADA servers, L3 = site ops/historian. Attacks flow *down* toward L0/L1, so safety depends on keeping IT and people out of the lower levels.

Q6. What sits at Purdue Level 3.5, and what is its purpose?

  • A. Level 3.5 is the physical process layer where sensors report
  • B. The IDMZ — the OT/IT boundary hosting jump hosts, proxies, and brokers
  • C. The enterprise ERP zone
  • D. The PLC control layer
Answer **B. The IDMZ (Industrial DMZ).** L3.5 is the **boundary between OT (L0–L3) and IT (L4–L5)**. It hosts jump hosts, proxies, and message brokers so no IT system or human reaches the control layers directly. This is where PAM belongs — make a brokered jump host the *only* ingress into OT.

Q7. The Mirai botnet compromised hundreds of thousands of IoT devices. What was its primary infection technique?

  • A. Exploiting a zero-day in MQTT brokers
  • B. MITM of unsigned OTA firmware updates
  • C. Cracking WPA2 on smart-home Wi-Fi
  • D. Scanning for open Telnet (23/2323) and trying default/factory credentials
Answer **D.** Mirai scanned the internet for open **Telnet (23/2323)** and tried a built-in list of **default credentials**, enlisting cameras/DVRs/routers into a **DDoS** botnet. **Exam lesson: default creds + an exposed management service = mass compromise.** The fix class is disable Telnet, change/rotate defaults, and vault device credentials.

Q8. In an ICS, which component is the operator-facing screen used to monitor and issue commands to the process?

  • A. PLC
  • B. Historian
  • C. HMI
  • D. RTU
Answer **C. HMI (Human-Machine Interface).** It is the operator's screen (typically at Purdue L2 with SCADA servers). The **PLC** is the field controller running the logic (L1); the **Historian** is the time-series database of process values (L3); the **RTU** is a remote field controller. Don't confuse the operator screen (HMI) with the controller (PLC).

Q9. Which statement best distinguishes SCADA, DCS, and PLC?

  • A. SCADA = distributed supervisory monitoring; DCS = in-plant process control; PLC = the field controller both use
  • B. They are three names for the same device
  • C. SCADA runs the logic; PLC supervises multiple plants; DCS is a database
  • D. DCS is geographically distributed; SCADA is confined to one plant
Answer **A.** **SCADA** = geographically **distributed** supervisory monitoring/control; **DCS** = process control within a **single plant**; **PLC** = the ruggedized **field controller** that actually runs the logic (used by both SCADA and DCS). Option D swaps the SCADA/DCS scope — a classic trap.

Q10. Which standard defines OT security in terms of zones and conduits, grouping assets by trust and allowing traffic only through controlled pathways?

  • A. OWASP IoT Top 10
  • B. IEC 62443
  • C. PCI DSS
  • D. NIST 800-53 AC family
Answer **B. IEC 62443** (ISA/IEC 62443). Assets of equal trust/risk go into a **zone**; traffic between zones is permitted only through a defined **conduit**. Practically: deny IT→OT by default, allow-list only, and pair with unidirectional gateways. The OWASP IoT Top 10 is for IoT device weaknesses, not OT zoning.

Q11. You subscribe to # on an unauthenticated MQTT broker and instantly see every device's messages, then publish a spoofed reading that a controller accepts. Which OWASP IoT theme does this illustrate?

  • A. Insecure network services (no authentication on the broker)
  • B. Physical debug-port exposure
  • C. Insecure OTA update mechanism
  • D. Weak RF pairing
Answer **A. Insecure network services.** The broker requires no authentication, so `#` (the multi-level wildcard) lets anyone **read every topic** and **inject** on any topic — a trust failure, not a code bug. The control is to require broker auth/TLS and, at the architecture level, segment and broker access (PAM). It maps to the same default/weak-credential family that tops the OWASP IoT Top 10.

Q12. A Modbus client reads and writes a PLC's registers with no login and no encryption. What is the primary reason, and the correct defense?

  • A. The engineer forgot to enable Modbus's built-in TLS; enable it
  • B. Modbus authenticates by MAC address; spoof-protect the switch
  • C. The PLC firmware is out of date; patch it to add auth
  • D. Modbus has no authentication/encryption by design; the defense is network segmentation, not the protocol
Answer **D.** Legacy OT protocols like **Modbus assume a trusted, isolated network** — they have **no built-in auth or crypto**, so there is nothing to "turn on." The durable defense is **segmentation, IEC 62443 zones/conduits, and brokered access**, keeping writes off the wire from untrusted sources. (OPC UA is the modern, security-capable alternative.)

Q13. Which reconnaissance approach lets you gauge how many Modbus or MQTT devices are exposed on the internet without connecting to any of them?

  • A. Nmap SYN scan of the target's /16
  • B. Modbus FC3 read against each host
  • C. mosquitto_sub -t '#' against each host
  • D. Query the Shodan/Censys index (passive)
Answer **D. Query the Shodan/Censys index.** Shodan and Censys maintain a **pre-built index** of internet-exposed devices, so searching (e.g. `port:502`) returns a **count and metadata** without you touching any device — passive recon. Options A, B, C are all *active* connections to systems you don't own, which is exactly what OT safety forbids.

Q14. A vendor needs occasional remote access to a PLC at Purdue L1. Which design aligns with the module's PAM guidance?

  • A. Time-boxed, VPN-less Remote Access brokered through a jump host in the IDMZ, with MFA and session recording
  • B. Give the vendor a standing site-to-site VPN straight to the PLC subnet
  • C. Publish the PLC's HMI to the internet behind a strong password
  • D. Share the PLC's default credentials over email for the maintenance window
Answer **A.** No human or vendor touches L0/L1 directly. Route the vendor through a **jump host in the IDMZ (L3.5)** using **time-boxed (JIT) Remote Access**, **MFA**, and **session recording** — never a standing VPN to the plant floor. CyberArk mapping: **Remote Access** for vendors, **PSM/PSMP** as the sole ingress, **CPM** to vault/rotate the device credential.

Q15. The recurring #1 weakness across the OWASP IoT Top 10 — and the root cause behind Mirai — is:

  • A. Lack of a secure update mechanism
  • B. Insecure data transfer without TLS
  • C. Weak, guessable, or hardcoded (default) passwords
  • D. Insufficient privacy protection
Answer **C. Weak/guessable/hardcoded (default) passwords.** It is the perennial top IoT weakness and the exact vector Mirai exploited over Telnet. Others (insecure update, insecure data transfer, privacy) are real but secondary. Fix class: change/rotate defaults, disable Telnet, and **vault + rotate device credentials** (PAM/CPM). Cite the official OWASP page rather than paraphrasing on the job.

Score yourself

  • 13–15: solid — move on, revisit missed items in facts.md.
  • 10–12: re-read the protocol/port table and the Purdue-model + IEC 62443 sections.
  • < 10: re-read README.md fully and redo the lab-walkthrough.md.